Transformer Wiring Chart 480v ( 3ø + GC - 208Y / 120V (3ø + N + EG)













TRANSFORMER WIRING CHART 480v ( 3ø + GC - 208Y / 120V (3ø + N + EG)












    PRIMARY SECONDARY
TXMR   KVA RATING MAX kVA     Note 1 CURRENT FUSE/BKR ø             WIRE G.C. Note 2 COND. SIZE CURRENT FUSE/ BKR WIRE       ø & N. SIZE E.G COND. SIZE
6 5.76 7.2 20 12 8 ½ 16.7 20 10 10 ½"
9 8.64 10.8 30 10 8 ½ 25 30 8 10 3/4"
15 14.4 18.0 40 8 8 3∕4 41.6 50 6 10 1 ¼"
30 28.8 36.1 50 6 8 1 83.3 100 2 6 1 ½"
45 43.2 54.1 70 4 4 1 ¼ 125 150 2∕0 6 2"
75 72 90.2 125 1 1 1 ¼ 208 250 300 2 3"
112 ½ 112 ½ 135 175 2∕0 1∕0 2 312 400 500 2 3 ½"
150 144 180 250 250 250 2 ½ 416 500 2 runs 250 2#1 2-3"
225 225 270 350 500 500 3 625 800 2 runs 500 2#1∕0 2-3 ½"
300 288 361 500 2 runs 250 2#3∕0 2-2½ 833 1000 3 runs 400 3#2∕0 3-3 ½"












Notes:






















1 Maximum load transformer is not to exceed the figures in this column.
2 The equipment ground conductors from the transformer back to the service entrance ground must not be smaller than this neutral ground conductor (GC).
3 If the secondary panel, switchboard, or MGC is more than 25 feet away from the transformer, overcurrent protection shall be provided at the transformer.